Instruction manual
–
AQ G3x7 Generator protection IED
125 (211
)
Figure 3-75: Output signals of the impedance protection function.
o
The operation of the impedance protection may be blocked either by parameter setting
(IMP21_Z-_EPar_equ_Off) or by binary input (IMP21_Z-_Blk_GrO_)
o
Starting in phase L1 if this phase is involved in the fault (IMP21_Z-StL1_GrI),
o
Starting in phase L2 if this phase is involved in the fault (IMP21_Z-StL2_GrI),
o
Starting in phase L2 if this phase is involved in the fault (IMP21_ZnStL3_GrI),
o
General start if any of the phases is involved in the fault (IMP21_Z-St_GrI),
o
A trip command is generated after the timer Delay is expired. This timer is started if the
zone is started and if trip command is required too, as it is set, using the parameter IMP21_
StOnly_BPar. The time delay is set by the timer parameter IMP21_Z-Del_TPar.
Table 3-56: General phase identification of the distance protection function.
The separate phase identification signals for Zones 2-5 are not published.