Instruction manual
–
AQ G3x7 Generator protection IED
78 (211
)
3.2.10.4
The fourier calculation
These modules calculate the basic Fourier current components of the phase currents
individually. These modules belong to the preparatory phase.
Figure 3-43 Schema of the Fourier calculation
The inputs are the sampled values of:
•
The three phase currents of the primary side (IL1, IL2, IL3)
The outputs are the basic Fourer components of the analyzed currents (IL1Four, IL2Four,
IL3Four).
3.2.10.5
The negative phase sequence calculation
This module calculates the negative phase sequence components based on the Fourier
components of the phase currents. This module belongs to the preparatory phase. The
inputs are the basic Fourier components of the phase currents (IL1Four, IL2Four, IL3Four).
The output is the basic Fourier component of the negative sequence current component
(INegFour).