sequence components, etc.) The number of the configured binary signals for recording is
limited to 64. During the operation of the function, the pre-fault signals are preserved for the
time duration as defined by the parameter
“
PreFault
”
. The fault duration is limited by the
parameter
“
MaxFault
”
but if the triggering signal resets earlier, this section is shorter. The
post-fault signals are preserved for the time duration as defined by the parameter
“
PostFault
”
. During or after the running of the recording, the triggering condition must be reset for a
new recording procedure to start.
The records are stored in standard COMTRADE format.
•
The configuration is defined by the file .cfg,
•
The data are stored in the file .dat,
•
Plain text comments can be written in the file .inf.
The procedure for downloading the records includes a downloading of a single compressed
.zip-file. Downloading can be initiated from a web browser tool or from the software tools.
This procedure assures that the three component files (.cfg, .dat and .inf) are stored in the
same location. The evaluation can be performed using any COMTRADE evaluator software,
e.g. Arcteq’s AQview software. Consult your nearest Arcteq representative for availability.
The symbol of the function block in the AQtivate 300 software
The function block of the disturbance recorder function is shown in figure bellow. This block
shows all binary input and output status signals that are applicable in the AQtivate 300
software.
Figure 3-109: The function block of the disturbance recorder function
The binary input and output status signals of the dead line detection function are listed in
tables below.