Instruction manual
–
AQ G3x7 Generator protection IED
135 (211
)
number”), the subsequent
impedance value is required to enter into the rectangle within the
running time of the timer. The running time is a parameter setting (“Dead time”).
The procedure is processed for each line-to-line loop. The result is the setting of three
internal status variables. This indicates that the calculated impedance performed the
required number of pole slips.
Figure 3-82 Principal scheme of the Quadrilateral characteristic decision
Input values
The input values are calculated by the module Z_CALC.
Table 3-61The input calculated impedances of the Quadrilateral characteristics module
Calculated value
Dim.
Explanation
RL1L2+j XL1L2
ohm
Calculated impedance in the fault loop L1L2
RL2L3+j XL2L3
ohm
Calculated impedance in the fault loop L2L3
RL3L1+j XL3L1
ohm
Calculated impedance in the fault loop L3L1
Output values
Table 3-62 The output status signals of the Quadrilateral characteristic module
Output values
Explanation
PsL1L2_1
The impedance in the fault loop L1L2 performed the given number of
pole slips