Instruction manual
–
AQ G3x7 Generator protection IED
80 (211
)
Parameter
Setting value, range
and step
Description
Operation
Off
DefinitTime
IEC Inv
IEC VeryInv
IEC ExtInv
IEC LongInv
ANSI Inv
ANSI ModInv
ANSI VeryInv
ANSI ExtInv
ANSI LongInv
ANSI LongVeryInv
ANSI LongExtInv
Operating mode selection of the function. Can be disabled,
Definite time or IDMT operation based into IEC or ANSI/IEEE
standards.
Default setting is “DefinitTime”
Start current
5…2
00 %, by step of
1%. Default 50 %.
Pick-up current setting of the function. Setting range is from
5% of nominal current to 400% with step of 1 %. Default setting
is 200 % of nominal current.
Min Delay
0…60000 ms, by step
of 1 ms. Default 100
ms.
Minimum operating delay setting for the IDMT characteristics.
Additional delay setting is from 0 ms to 60000 ms with step of
1 ms. Default setting is 100 ms.
Definite
delay time
0…60000 m
s by step
of 1 ms. Default 100
ms.
Definite time operating delay setting. Setting range is from 0
ms to 60000 ms with step of 1 ms. Default setting is 100 ms.
This parameter is not in use when IDMT characteristics is
selected for the operation.
Reset delay
0…60000 ms by step
of 1 ms. Default 100
ms.
Settable reset delay for definite time function and IEC IDMT
operating characteristics. Setting range is from 0 ms to 60000
ms with step of 1 ms. Default setting is 100 ms. This parameter
is in use with definite time and IEC IDMT chartacteristics-
Time Mult
100
…
6000 by step of
1. Default 100.
Time multiplier / time dial setting of the IDMT operating
characteristics. This parameter is not in use with definite time
characteristics.