![Arcteq AQ G397 Скачать руководство пользователя страница 89](http://html1.mh-extra.com/html/arcteq/aq-g397/aq-g397_instruction-manual_2964934089.webp)
Instruction manual
–
AQ G3x7 Generator protection IED
89 (211
)
Figure 3-52: Third harmonic undervoltage independent time characteristic
t
OP
(seconds) theoretical operating time if G < G
S
, according to parameter setting value,
G
measured value of the characteristic quantity, Fourier third harmonic of the neutral
voltage,
G
S
setting value of the characteristic quantity.
Structure of third harmonic undervoltage protection
Figure below shows the structure of the definite time third harmonic undervoltage protection
(HIZ64) algorithm.
Figure 3-53: Structure of third harmonic undervoltage protection.