Instruction manual
–
AQ G3x7 Generator protection IED
56 (211
)
The algorithm generates a start signal based on the Fourier components of the residual
current in case if the user set pick-up value is exceeded. Trip signal is generated after the set
definite time delay.
The function includes a blocking signal input which can be configured by user from either
IED internal binary signals or IED binary inputs through the programmable logic.
Table 3-19: Setting parameters of the residual time overcurrent function
Parameter
Setting value, range
and step
Description
Operation
Off
DefinitTime
IEC Inv
IEC VeryInv
IEC ExtInv
IEC LongInv
ANSI Inv
ANSI ModInv
ANSI VeryInv
ANSI ExtInv
ANSI LongInv
ANSI LongVeryInv
ANSI LongExtInv
Operating mode selection of the function. Can be disabled,
Definite time or IDMT operation based into IEC or
ANSI/IEEE standards. Default setting is “DefinitTime”
Start current
1
…
200 %, by step of
1%. Default 50 %.
Pick-up current setting of the function. Setting range is from
1% of nominal current to 200% with step of 1 %. Default
setting is 50 % of nominal current.
Min Delay
0…60000 ms, by step
of 1 ms. Default 100
ms.
Minimum operating delay setting for the IDMT
characteristics. Additional delay setting is from 0 ms to
60000 ms with step of 1 ms. Default setting is 100 ms.
Definite delay
time
0…60000 ms by step
of 1 ms. Default 100
ms.
Definite time operating delay setting. Setting range is from 0
ms to 60000 ms with step of 1 ms. Default setting is 100 ms.
This parameter is not in use when IDMT characteristics is
selected for the operation.
Reset time
0…60000 ms by step
of 1 ms. Default 100
ms.
Settable reset delay for definite time function and IEC IDMT
operating characteristics. Setting range is from 0 ms to
60000 ms with step of 1 ms. Default setting is 100 ms. This
parameter is in use with definite time and IEC IDMT
chartacteristics-
Time Mult
0.05…9
99.00 by step
of 0.01. Default 1.00.
Time multiplier / time dial setting of the IDMT operating
characteristics. Setting range is from 0.05 to 999.00 with
step of 0.01. This parameter is not in use with definite time
characteristics.
3.2.6
V
OLTAGE DEPENDENT OVERCURRENT
(51V)
When overcurrent protection function is applied and the current in normal operation can be
high, related to the lowest fault current then the correct setting is not possible based on current
values only. In this case however, if the voltage during fault is considerably below the lowest