63 (211
)
Figure 3-34: Structure of the directional overcurrent protection algorithm.
Based on the measured voltages and currents the function block selects the lowest
calculated loop impedance of the six loops (L1L2, L2L3, L3L1, L1N, L2N, L3N).
Based on the loop voltage and loop current of the selected loop the directional
decision is “Forward” if the voltage and the current is sufficient for directional
decision, and the angle difference between the vectors is inside the set operating
characteristics. If the angle difference between the vectors is outside of the set
characteristics the directional decision is “Backward”.