Instruction manual
–
AQ G3x7 Generator protection IED
62 (211
)
Table 3-20 Parameters of the voltage restrained overcurrent
Parameter
Setting value, range
and step
Description
Operation
Off
On
Operating mode selection of the function. Default setting is On.
Voltage
mode
Restrained
Controlled
Voltage mode selection of the function. Default setting is
Restrained.
Start
current
20
…3000 %, by step
of 1%
Pick-up setting of the function. Setting range is from 20% to
3000% of the configured nominal secondary current. Setting
step is 1 %. Default setting is 200 %
Uhighlimit
60…110 %, by step
of 1%
In "Voltage controlled" mode the function is enabled only when
the voltage is below "Uhighlimit" level. In "Voltage restrained"
mode the overcurrent pickup (and drop off) setting value is
multiplied by the k=Uactual/Unominal factor when the voltage is
within the Uhighlimit - Ulowlimit range. When the voltage is
below Uhighlimit the current setting slope is linearized by
parameters Ulowlimit and Ilowlimit.
Ulowlimit
20…60 %, by step of
1%
Lower voltage range of the current setting slope k.
Ilowlimit
20…60 %, by step of
1%
Current setting slope k startpoint.
3.2.7
T
HREE
-
PHASE DIRECTIONAL OVERCURRENT
ID
IR
>,ID
IR
>>(67)
The directional three-phase overcurrent protection function can be applied on networks
where the overcurrent protection must be supplemented with a directional decision. The
inputs of the function are the Fourier basic harmonic components of the three phase currents
and those of the three phase voltages. In the figure below is presented the structure of the
directional overcurrent protection algorithm.