Instruction manual
–
AQ G3x7 Generator protection IED
86 (211
)
Figure 3-50: The principal structure of the undervoltage function.
The general start signal is set active if the voltage of any of the three measured voltages is
below the level defined by pick-up setting value. The function generates a trip command
after the definite time delay has elapsed.
Table 3-32: Setting parameters of the undervoltage function
Parameter
Setting value, range
and step
Description
Operation
Off
1 out of 3
2 out of 3
All
Operating mode selection for the function. Operation can be
either disabled “Off” or the operating mode can be selected
to monitor single phase undervoltage, two phases
undervoltage or all phases undervoltage condition. Default
setting is “1 out of 3” which means that any phase under the
setting limit will cause operation.
Start voltage
30…130 % by step of
1 %
Voltage pick-up setting. Default setting is 90 %.
Block
voltage
0…20 % by step of 1
%
Undervoltage blocking setting. This setting prevents the
function from starting in undervoltage condition which is
caused for example from opened breaker. Default setting is
10 %.
Start signal
only
Activated
Deactivated
Selection if the function issues ei
ther “Start” signal alone or
both “Start” and after set time delay “Trip” signal.
Default is
that both signals are generated (=deactivated).
Reset ratio
1…10% by step of
1%
Undervoltage protection reset ratio, default setting is 5%
Time delay
0…60000 ms
by step
of 1 ms.
Operating time delay setting for the “Trip” signal from the
“Start” signal.
Default setting is 100 ms.