Instruction manual
–
AQ G3x7 Generator protection IED
162 (211
)
Table 3-70: Setting parameters of the Common function
Parameter
Setting value, range
and step
Description
Ext LR
Source
0
0 means no external local/remote setting is enabled, the local
LCD touch-screen is the only source of toggling.
3.3.2
T
RIP LOGIC
(94)
The simple trip logic function operates according to the functionality required by the IEC
61850 standard for the “Trip logic logical node”.
This simplified software module can be
applied if only three-phase trip commands are required, that is, phase selectivity is not
applied. The function receives the trip requirements of the protective functions implemented
in the device and combines the binary signals and parameters to the outputs of the device.
Figure 3-1 Operation logic of the trip logic function.
The trip requirements can be programmed by the user. The aim of the decision logic is to
define a minimal impulse duration even if the protection functions detect a very short-time
fault.
3.3.2.1
Application example