Table 3-4 Floating point parameters of the current input function
Table 3-5 Online measurements of the current input function
NOTE1: The scaling of the Fourier basic component is such that if pure sinusoid 1A RMS
of the rated frequency is injected, the displayed value is 1A. The displayed value does not
depend on the parameter setting values “Rated Secondary”.
NOTE2: The reference of the vector position depends on the device configuration. If a
voltage input module is included, then the reference vector (vector with angle 0 degree) is
the vector calculated for the first voltage input channel of the first applied voltage input
module. If no voltage input module is configured, then the reference vector (vector with
angle 0 degree) is the vector calculated for the first current input channel of the first applied
current input module. (The first input module is the one, configured closer to the CPU
module.)
3.1.2
V
OLTAGE MEASUREMENT AND SCALING
If the factory configuration includes a voltage transformer hardware module, the voltage
input function block is automatically configured among the software function blocks.
Separate voltage input function blocks are assigned to each voltage transformer hardware
module.
A voltage transformer hardware module is equipped with four special intermediate voltage
transformers. As usual, the first three voltage inputs receive the three phase voltages (UL1,
UL2, UL3), the fourth input is reserved for zero sequence voltage or for a voltage from the
other side of the circuit breaker for synchro switching.