Instruction manual
–
AQ G3x7 Generator protection IED
146 (211
)
Figure 3-88: The function block of the loss of excitation protection function.
Table 3-64: Setting parameters of the impedance protection function.
Parameter
Setting value, range
and step
Description
Operation
Off, NoCompound,
FWCompound,
BWCompound
Operating mode selection for the function. Default setting is
NoCompound.
Impedance
start only
Activated
Deactivated
Selection if the function issues either “Start” signal alone or
both “Start” and after set time delay “Trip” signal.
Default is
that both signals are generated (=deactivated).
IPh Base
Sens
10…30%
by step of 1 Minimum current setting for phase currents. Default setting is
20.
IRes Base
Sens
10…50%
by step of 1 Minimum current setting for residual current. Default setting
is 10.
IRes bias
5…30%
by step of 1
Slope of the percentage characteristic for earth-fault
detection. Default setting is 10.
PsImpAng
0…90 deg
by step of
1
Positive impedance angle. Default setting is 10.
OfsImpRch
-150.00
…
150.00
Ohm by step of 0.01.
Offset impedance reach. Default setting is 0.00.
PsImpRch
0.10
…
250.00 Ohm by
step of 0.01.
Positive impedance reach. Default setting is 10.00.
Zone1 (Xo-
X1)/3X1
0.00
…
5.00 by step of
0.01.
The zero sequence current compensation factor, calculated
with X values. Default setting is 0.00.
Zone1 (Ro-
R1)/3R1
0.00
…
5.00 by step of
0.01.
The zero sequence current compensation factor, calculated
with R values. Default setting is 0.00.
Time delay
0
…
60000ms by step
of 1.
Operation time delay. Default setting is 500.