Instruction manual
–
AQ G3x7 Generator protection IED
69 (211
)
Characteristic
Angle
-
180…180 deg by
step of 1 deg
The base angle of the operating characteristics.
Operation
Off
Definit time
IEC Inv
IEC VeryInv
IEC ExtInv
IEC LongInv
ANSI Inv
ANSI ModInv
ANSI VeryInv
ANSI ExtInv
ANSI LongInv
ANSI LongVeryInv
ANSI LongExtInv
Selection of the function disabled and the timing
characteristics. Operation when enabled can be either
Definite time or IDMT characteristic.
Start current
1
…200 % by step of
1%
Pick-up residual current
Time Mult
0.05…999 by step of
0.01
Time dial/multiplier setting used with IDMT operating
time characteristics.
Min. Time
0…60000 ms by step
of 1 ms
Minimum time delay for the inverse characteristics.
Def Time
0…60000 ms by step
of 1 ms
Definite operating time
Reset Time
0…60000 ms by step
of 1 ms
Settable function reset time
3.2.9
C
URRENT
U
NBALANCE
I2>
(60)
The current unbalance protection function can be applied to detect unexpected asymmetry in
current measurement.
The applied method selects maximum and minimum phase currents (fundamental Fourier
components). If the difference between them is above the setting limit, the function generates
a start signal.
Structure of the current unbalance protection function is presented in the figure below