Restrained differential characteristics
The restrained differential characteristic is drawn in the figure below.
Additionally separate status-
signals are set to “true” value if the differential currents in the
individual phases are above
the limit, set by parameter (see “Unrestrained differential
function”).
Unrestrained differential characteristics
If the calculated differential current is very high then the differential characteristic is not
considered anymore, because separate status-
signals for the phases are set to “true” value
if the differential currents in the individual phases are above the limit, defined by parameter
setting. The decisions of the phases are connected in OR gate to result the general start
status signal.
Measured values
The measured and displayed values of the generator differential protection function are
listed in below table.