Instruction manual
–
AQ G3x7 Generator protection IED
75 (211
)
Table 3-26 The resetting constants of the standard dependent time characteristics
The inverse type characteristics are also combined with a minimum time delay, the value of
which is set by user parameter TOC46_MinDel_TPar_ (Min. Time Delay)
3.2.10.3
Structure of the negative sequence overcurrent protection algorithm
Figure below shows the structure of the negative sequence overcurrent protection (TOC46)
algorithm