Maximum permitted interrupt time
< 60 ms with 110 VDC
DC ripple
< 15 %
Terminal block connection
Terminal block
Phoenix Contact MSTB 2,5/5-ST-5,08
Solid or stranded wire
Maximum wire diameter
2.5 mm
2
Other
Minimum recommended fuse rating
MCB C2
Table. 9.1.2.1 - 252. Power supply model B
Rated values
Rated auxiliary voltage
18…72 VDC
Power consumption
< 7 W
< 15 W
Maximum permitted interrupt time
< 90 ms with 24 VDC
DC ripple
< 15 %
Terminal block connection
Terminal block
Phoenix Contact MSTB 2,5/5-ST-5,08
Solid or stranded wire
Maximum wire diameter
2.5 mm
2
Other
Minimum recommended fuse rating
MCB C2
9.1.2.2 CPU communication ports
Table. 9.1.2.2 - 253. Front panel local communication port.
Port
Port media
Copper Ethernet RJ-45
Number of ports
1
Port protocols
PC-protocols
FTP
Telnet
Features
Data transfer rate
100 MB
System integration
Cannot be used for system protocols, only for local programming
Table. 9.1.2.2 - 254. Rear panel system communication port A.
Port
Port media
Copper Ethernet RJ-45
Number of ports
1
Features
A
AQ
Q-C215
-C215
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00040
321
Содержание AQ-C215
Страница 1: ...AQ C215 Capacitor bank protection IED Instruction manual ...
Страница 2: ......
Страница 297: ...Figure 7 4 179 Example block scheme A AQ Q C215 C215 Instruction manual Version 2 07 Arcteq Relays Ltd IM00040 295 ...
Страница 318: ...Figure 8 14 200 Device installation A AQ Q C215 C215 Instruction manual Version 2 07 316 Arcteq Relays Ltd IM00040 ...
Страница 347: ...10 Ordering information A AQ Q C215 C215 Instruction manual Version 2 07 Arcteq Relays Ltd IM00040 345 ...