Signal
Description
Signal
Description
POW1 3PH
Reactive power (Q
MVar)
Three-phase reactive power
in megavars
Alg f Fast
Fast frequency algorithm
POW1 3PH
Tan(phi)
Three-phase tangent phi
Alg f avg
Average frequency algorithm
POW1 3PH
Cos(phi)
Three-phase cosine phi
Frequency based
protections blocked
When true ("1"), all frequency-based
protections are blocked.
3PH PF
Three-phase power factor
f atm. Protections (when not
measurable returns to
nominal)
Frequency at the moment. If the system
nominal is set to 50 Hz, this will show "50
Hz".
Neutral
conductance G
(Pri)
Primary neutral
conductance
f atm. Display (when not
measurable is 0 Hz)
Frequency at the moment. If the frequency
is not measurable, this will show "0 Hz".
Neutral
susceptance B
(Pri)
Primary neutral
susceptance
f meas qlty
Quality of tracked frequency
Neutral
admittance Y (Pri)
Primary neutral admittance
f meas from
Indicates which of the three voltage or
current channel frequencies is used by the
relay.
Neutral
admittance Y
(Ang)
Neutral admittace angle
SS1.meas.frqs
Synchrocheck – the measured frequency
from voltage channel 1
I01 Resistive
component (Pri)
Primary resistive
component I01
SS2.meas.frqs
Synchrocheck – the measured frequency
from voltage channel 2
I01 Capacitive
component (Pri)
Primary capacitive
component I01
Enable f based functions
Status of this signal is active when
frequency-based protection functions are
enabled.
Table. 5.6.4 - 193. Digital recording channels – Binary signals.
Signal
Description
Signal
Description
DIx
Digital input 1...11
Timer x Output
Output of Timer 1...10
Open/close
control
buttons
Active if buttons I or 0 in the unit's
front panel are pressed.
Internal Relay Fault active
If the unit has an internal fault, this signal
is active.
Status
PushButton x
On
Status of Push Button 1...12 is ON
(Protection, control and
monitoring event signals)
(see the individual function description for
the specific outputs)
Status
PushButton x
Off
Status of Push Button 1...12 is
OFF
Always True/False
"Always false" is always "0". Always true is
always "1".
Forced SG in
use
Stage forcing in use
OUTx
Output contact statuses
SGx Active
Setting group 1...8 active
GOOSE INx
GOOSE input 1...64
Double
Ethernet LinkA
down
Double ethernet communication
card link A connection is down.
GOOSE INx quality
Quality of GOOSE input 1...64
Double
Ethernet LinkB
down
Double ethernet communication
card link B connection is down.
Logical Input x
Logical input 1...32
MBIO ModA
Ch x Invalid
Channel 1...8 of MBIO Mod A is
invalid
Logical Output x
Logical output 1...64
MBIO ModB
Ch x Invalid
Channel 1...8 of MBIO Mod B is
invalid
NTP sync alarm
If NTP time synchronization is lost, this
signal will be active.
A
AQ
Q-C215
-C215
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00040
247
Содержание AQ-C215
Страница 1: ...AQ C215 Capacitor bank protection IED Instruction manual ...
Страница 2: ......
Страница 297: ...Figure 7 4 179 Example block scheme A AQ Q C215 C215 Instruction manual Version 2 07 Arcteq Relays Ltd IM00040 295 ...
Страница 318: ...Figure 8 14 200 Device installation A AQ Q C215 C215 Instruction manual Version 2 07 316 Arcteq Relays Ltd IM00040 ...
Страница 347: ...10 Ordering information A AQ Q C215 C215 Instruction manual Version 2 07 Arcteq Relays Ltd IM00040 345 ...