Table. 5.4.7 - 91. Measured magnitude selection settings.
Name
Description
Range
Step Default
Measured
magnitude
Selection of phase-to-phase or phase-to-earth voltages. Additionally, the U3 or
U4 input can be assigned as the voltage channel to be supervised.
0: P-P
voltages
1: P-E
voltages
2: U3 input
(2LL-U3SS)
3: U4 input
(SS)
-
0: P-P
voltages
The selection of the AI channel in use is made with a setting parameter. In all possible input channel
variations the pre-fault condition is presented with a 20 ms averaged history value from -20 ms from
START or TRIP event.
Figure. 5.4.7 - 97. Selectable measurement magnitudes with 3LN+U4 VT connection.
Figure. 5.4.7 - 98. Selectable measurement magnitudes with 3LL+U4 VT connection (P-E voltages not available without residual
voltage).