• the dominant standard in many industries
• the simplest option to connect and configure
• uses less wiring and connections than other signals, thus greatly reducing initial setup costs
• good for travelling long distances, as current does not degrade over long connections like
voltage does
• less sensitive to background electrical noise
• detects a fault in the system incredibly easily since 4 mA is equal to 0 % output.
Milliampere (mA) outputs
AQ-200 series supports up to two (2) independent mA option cards. Each card has four (4) mA output
channels and one (1) mA input channel. If the device has an mA option card, enable mA outputs at
Control
→
Device IO
→
mA outputs. The outputs are activated in groups of two: channels 1 and 2 are
activated together, as are channels 3 and 4.
Table. 5.5.5 - 162. Main settings (output channels).
Name
Range
Default
Description
mA option
card 1
Enable mA output channels 1
and 2
0:
Disabled
1: Enabled
0:
Disabled
Enables and disables the outputs of the mA output
card 1.
Enable mA output channels 3
and 4
mA option
card 2
Enable mA output channels 5
and 6
0:
Disabled
1: Enabled
0:
Disabled
Enables and disables the outputs of the mA output
card 2.
Enable mA output channels 7
and 8
Table. 5.5.5 - 163. Settings for mA output channels.
Name
Range
Step
Default
Description
Enable mA
output
channel
0: Disabled
1: Enabled
-
0: Disabled
Enables and disables the selected mA output channel. If
the channel is disabled, the channel settings are hidden.
Magnitude
selection for
mA output
channel
0: Currents
1: Voltages
2: Powers
3: Impedance and
admittance
4: Other
-
0: Currents
Defines the measurement category that is used for mA
output control.
Magnitude
of mA
output
channel
(dependent on the
measurement
category selection)
-
(dependent on
the
measurement
category
selection)
Defines the measurement magnitude used for mA output
control. The available measurements depend on the
selection of the "Magnitude selection for mA output
channel" parameter.
Input value
1
-10
7
…10
7
0.001
0
The first input point in the mA output control curve.
Scaled mA
output
value 1
0.0000…24.0000mA 0.0001mA 0mA
The mA output value when the measured value is equal
to or less than Input value 1.
Input value
2
-10
7
…10
7
0.001
1
The second input point in the mA output control curve.
Scaled mA
output
value 2
0.0000…24.0000mA 0.0001mA 0mA
The mA output value when the measured value is equal
to or greater than Input value 2.
A
AQ
Q-C215
-C215
Instruction manual
Version: 2.07
218
© Arcteq Relays Ltd
IM00040
Содержание AQ-C215
Страница 1: ...AQ C215 Capacitor bank protection IED Instruction manual ...
Страница 2: ......
Страница 297: ...Figure 7 4 179 Example block scheme A AQ Q C215 C215 Instruction manual Version 2 07 Arcteq Relays Ltd IM00040 295 ...
Страница 318: ...Figure 8 14 200 Device installation A AQ Q C215 C215 Instruction manual Version 2 07 316 Arcteq Relays Ltd IM00040 ...
Страница 347: ...10 Ordering information A AQ Q C215 C215 Instruction manual Version 2 07 Arcteq Relays Ltd IM00040 345 ...