NO
NOTE!
TE!
BI1, HSO1 and HSO2 are not visible in the
Binary inputs and Binary outputs menus
(
Control
→
Device I/O), they can only be programmed in the arc matrix menu
(
Protection
→
Arc protection
→
I/O
→
Direct output control and HSO control).
8.8 RTD input module (optional)
Figure. 8.8 - 189. RTD input module connectors.
The RTD input module is an add-on module with eight (8) RTD input channels. Each input supports
2-wire, 3-wire and 4-wire RTD sensors. The sensor type can be selected with software for two groups,
four channels each. The card supports Pt100 and Pt1000 sensors
A
AQ
Q-C215
-C215
Instruction manual
Version: 2.07
308
© Arcteq Relays Ltd
IM00040
Содержание AQ-C215
Страница 1: ...AQ C215 Capacitor bank protection IED Instruction manual ...
Страница 2: ......
Страница 297: ...Figure 7 4 179 Example block scheme A AQ Q C215 C215 Instruction manual Version 2 07 Arcteq Relays Ltd IM00040 295 ...
Страница 318: ...Figure 8 14 200 Device installation A AQ Q C215 C215 Instruction manual Version 2 07 316 Arcteq Relays Ltd IM00040 ...
Страница 347: ...10 Ordering information A AQ Q C215 C215 Instruction manual Version 2 07 Arcteq Relays Ltd IM00040 345 ...