Figure. 5.6.1 - 153. Secondary circuit fault in phase L1 wiring.
When a fault is detected and all conditions are met, the CTS timer starts counting. If the situation
continues until the set time has passed, the function issues an alarm.
Figure. 5.6.1 - 154. Primary circuit fault in phase L1 wiring.
In this example, distinguishing between a primary fault and a secondary fault is impossible. However,
the situation meets the function's activation conditions, and if this state (secondary circuit fault)
continues until the set time has passed, the function issues an alarm. This means that the function
supervises both the primary and the secondary circuit.
A
AQ
Q-C215
-C215
Instruction manual
Version: 2.07
230
© Arcteq Relays Ltd