Name
Range
Default
Description
Group 32 variation (AI change)
0: Var 1
1: Var 2
2: Var 3
3: Var 4
4: Var 5
5: Var 7
4: Var 5
Selects the variation of the analog signal change.
Setting the analog change deadbands
Table. 6.1.8 - 232. Analog change deadband settings.
Name
Range
Step
Default
Description
General deadband
0.1…10.0%
0.1%
2%
Determines the general data reporting deadband settings.
Active energy deadband
0.1…1000.0kWh 0.1kWh 2kWh
Determines the data reporting deadband settings for this
measurement.
Reactive
energy deadband
0.1…1000.0kVar 0.1kVar 2kVar
Determines the data reporting deadband settings for this
measurement.
Active power deadband
0.1…1000.0kW
0.1kW
2kW
Determines the data reporting deadband settings for this
measurement.
Reactive
power deadband
0.1…1000.0kVar 0.1kVar 2kVar
Determines the data reporting deadband settings for this
measurement.
Apparent
power deadband
0.1…1000.0kVA
0.1kVA
2kVA
Determines the data reporting deadband settings for this
measurement.
Power factor deadband
0.01…0.99
0.01
0.05
Determines the data reporting deadband settings for this
measurement.
Frequency deadband
0.01…1.00Hz
0.01Hz
0.1Hz
Determines the data reporting deadband settings for this
measurement.
Current deadband
0.01…50.00A
0.01A
5A
Determines the data reporting deadband settings for this
measurement.
Residual
current deadband
0.01…50.00A
0.01A
0.2A
Determines the data reporting deadband settings for this
measurement.
Voltage deadband
0.01…5000.00V
0.01V
200V
Determines the data reporting deadband settings for this
measurement.
Residual
voltage deadband
0.01…5000.00V
0.01V
200V
Determines the data reporting deadband settings for this
measurement.
Angle
measurement deadband 0.1…5.0deg
0.1deg
1deg
Determines the data reporting deadband settings for this
measurement.
Integration time
0…10 000ms
1ms
-
Displays the integration time of the protocol.
6.1.9 IEC 101/104
The standards IEC 60870-5-101 and IEC 60870-5-104 are closely related. Both are derived from the
IEC 60870-5 standard. On the physical layer the IEC 101 protocol uses serial communication whereas
the IEC 104 protocol uses Ethernet communication. The IEC 101/104 implementation works as a slave
in the unbalanced mode.
For detailed information please refer to the IEC 101/104 interoperability document (
→
AQ-200 series
→
Resources
→
"AQ-200 IEC101 & IEC104 interoperability").
A
AQ
Q-C215
-C215
Instruction manual
Version: 2.07
280
© Arcteq Relays Ltd
IM00040
Содержание AQ-C215
Страница 1: ...AQ C215 Capacitor bank protection IED Instruction manual ...
Страница 2: ......
Страница 297: ...Figure 7 4 179 Example block scheme A AQ Q C215 C215 Instruction manual Version 2 07 Arcteq Relays Ltd IM00040 295 ...
Страница 318: ...Figure 8 14 200 Device installation A AQ Q C215 C215 Instruction manual Version 2 07 316 Arcteq Relays Ltd IM00040 ...
Страница 347: ...10 Ordering information A AQ Q C215 C215 Instruction manual Version 2 07 Arcteq Relays Ltd IM00040 345 ...