Name
Range
Default
Description
Device location
-
Unitlocation
Time
synchronization source
0: Internal
1: External
NTP
2: External
Serial
3: IRIG-B
0: Internal
If an external clock time synchronization source is available, the type is
defined with this parameter. In the internal mode there is no external
Timesync source. IRIG-B requires a serial fiber communication option
card.
Enable stage forcing
0: Disabled
1: Enabled
0: Disabled
When this parameter is enabled it is possible for the user to force the
protection, control and monitoring functions to different statuses like
START and TRIP. This is done in the function’s
Info page with the Force
status to parameter.
System phase rotating
order
0: A-B-C
1: A-C-B
0: A-B-C
Allows the user to switch the expected order in which the phase
measurements are wired to the unit.
Language
0: User
defined
1: English
2: Finnish
3: Swedish
4: Spanish
5: French
6: German
7: Russian
8:
Ukrainian
1: English
Changes the language of the parameter descriptions in the HMI. If the
language has been set to "Other" in the settings of the AQtivate setting
tool, AQtivate follows the value set into this parameter.
Clear events
0: -
1: Clear
0: -
Clears the event history recorded in the AQ-200 device.
LCD Contrast
0…255
120
Changes the contrast of the LCD display.
Return to default view
0…3600s
0s
If the user navigates to a menu and gives no input after a period of time
defined with this parameter, the unit automatically returns to the default
view. If set to 0 s, this feature is not in use.
LED test
0: -
1: Activated 0: -
When activated, all LEDs are lit up. LEDs with multiple possible colors
blink each color.
Reset latches
0: -
1: Reset
0: -
Resets the latched signals in the logic and the matrix. When a reset
command is given, the parameter automatically returns back to "-".
Measurement recorder 0: Disabled
1: Enabled
0: Disabled
Enables the measurement recorder tool, further configured in
Tools
→
Misc
→
Measurement recorder.
Reconfigure mimic
0: -
1:
Reconfigure
0: -
Reloads the mimic to the unit.
Table. 5.3 - 45. The
General menu read-only parameters
Name
Description
Serial number
The unique serial number identification of the unit.
Firmware version
The firmware software version of the unit.
Hardware configuration
The order code identification of the unit.
UTC time
The UTC time value which the device's clock uses.
A
AQ
Q-C215
-C215
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00040
89
Содержание AQ-C215
Страница 1: ...AQ C215 Capacitor bank protection IED Instruction manual ...
Страница 2: ......
Страница 297: ...Figure 7 4 179 Example block scheme A AQ Q C215 C215 Instruction manual Version 2 07 Arcteq Relays Ltd IM00040 295 ...
Страница 318: ...Figure 8 14 200 Device installation A AQ Q C215 C215 Instruction manual Version 2 07 316 Arcteq Relays Ltd IM00040 ...
Страница 347: ...10 Ordering information A AQ Q C215 C215 Instruction manual Version 2 07 Arcteq Relays Ltd IM00040 345 ...