![Arcteq AQ-C215 Скачать руководство пользователя страница 264](http://html1.mh-extra.com/html/arcteq/aq-c215/aq-c215_instruction-manual_2964938264.webp)
Please note that setting the number of available stages does not activate those stages, as they also
need to be enabled individually with the
PSx >/< Enabled parameter. When enabled an active
stage shows its current state (condition), the expected operating time and the time remaining to trip
under the activation parameters. If a stage is not active the
PSx>/< condition parameter will merely
display “Disabled”.
The function's outputs are START, TRIP and BLOCKED signals. The programmable stage function
uses a total of eight (8) separate setting groups which can be selected from one common source.
The function can operate on instant or time-delayed mode. Definite time (DT) delay can be selected in
the In time-delayed mode.
The inputs for the function are the following:
• operating mode selections
• setting parameters
• digital inputs and logic signals
• measured and pre-processed magnitudes.
The function's outputs are START, TRIP and BLOCKED signals which can be used for direct I/O
controlling and user logic programming. The function generates general time-stamped ON/OFF events
to the common event buffer from each of the three (3) output signals. In the instant operating mode the
function outputs START and TRIP events simultaneously with an equivalent time stamp. The time stamp
resolution is 1 ms. The function also provides a resettable cumulative counter for the START, TRIP and
BLOCKED events.
Analog values
The numerous analog signals have been divided into categories to help the user find the desired value.
Table. 5.7 - 201. Phase and residual current measurements (IL1, IL2, IL3, Io1 and Io2)
Name
Description
ILx ff (p.u.)
Fundamental frequency RMS value (in p.u.)
ILx 2
nd
h.
ILx 2
nd
harmonic value (in p.u.)
ILx 3
rd
h.
ILx 3
nd
harmonic value (in p.u.)
ILx 4
th
h.
ILx 4
nd
harmonic value (in p.u.)
ILx 5
th
h.
ILx 5
nd
harmonic value (in p.u.)
ILx 7
th
h.
ILx 7
nd
harmonic value (in p.u.)
ILx 9
th
h.
ILx 9
nd
harmonic value (in p.u.)
ILx 11
th
h.
ILx 11
nd
harmonic value (in p.u.)
ILx 13
th
h.
ILx 13
nd
harmonic value (in p.u.)
ILx 15
th
h.
ILx 15
nd
harmonic value (in p.u.)
ILx 17
th
h.
ILx 17
nd
harmonic value (in p.u.)
ILx 19
th
h.
ILx 19
nd
harmonic value (in p.u.)
ILx TRMS
ILx TRMS value (in p.u.)
ILx Ang
ILx Angle (degrees)
A
AQ
Q-C215
-C215
Instruction manual
Version: 2.07
262
© Arcteq Relays Ltd
IM00040
Содержание AQ-C215
Страница 1: ...AQ C215 Capacitor bank protection IED Instruction manual ...
Страница 2: ......
Страница 297: ...Figure 7 4 179 Example block scheme A AQ Q C215 C215 Instruction manual Version 2 07 Arcteq Relays Ltd IM00040 295 ...
Страница 318: ...Figure 8 14 200 Device installation A AQ Q C215 C215 Instruction manual Version 2 07 316 Arcteq Relays Ltd IM00040 ...
Страница 347: ...10 Ordering information A AQ Q C215 C215 Instruction manual Version 2 07 Arcteq Relays Ltd IM00040 345 ...