Table. 5.5.3 - 152. I/O.
Signal
Range
Description
Objectx Open input
("Objectx Open Status
In")
Digital input or
other logical
signal selected
by the user
(SWx)
A link to a physical digital input. The monitored object's OPEN status. "1" refers
to the active open state of the monitored object. If IEC 61850 is enabled,
GOOSE signals can be used for status indication.
Objectx Close input
("Objectx Close Status
In")
A link to a physical digital input. The monitored object's CLOSE status.
"1" refers to the active close state of the monitored object. If IEC 61850 is
enabled, GOOSE signals can be used for status indication.
WD Object In
("Withdrw.CartIn.Status
In")
A link to a physical digital input. The monitored withdrawable object's position
is IN. "1" means that the withdrawable object cart is in. If IEC 61850 is
enabled, GOOSE signals can be used for status indication.
WD Object Out
("Withdrw.CartOut.Status
In")
A link to a physical digital input. The monitored withdrawable object's position
is OUT. "1" means that the withdrawable object cart is pulled out. If IEC 61850
is enabled, GOOSE signals can be used for status indication.
Object Ready
(Objectx Ready status
In")
A link to a physical digital input. Indicates that status of the monitored object.
"1" means that the object is ready and the spring is charged for a close
command. If IEC 61850 is enabled, GOOSE signals can be used for status
indication.
Syncrocheck permission
("Sync.Check status In")
A link to a physical digital input or a synchrocheck function. "1" means that the
synchrocheck conditions are met and the object can be closed. If IEC 61850 is
enabled, GOOSE signals can be used for status indication.
Objectx Open command
("Objectx Open
Command")
OUT1…OUTx
The physical "Open" command pulse to the device's output relay.
Objectx Close command
("Objectx Close
Command")
The physical "Close" command pulse to the device's output relay.
Table. 5.5.3 - 153. Operation settings.
Name
Range
Step Default
Description
Breaker
traverse
time
0.02…500.00
s
0.02
s
0.2 s
Determines the maximum time between open and close statuses when the
breaker switches. If this set time is exceeded and both open and closed
status inputs are active, the status "Bad" is activated in the "Objectx Breaker
status" setting. If neither of the status inputs are active after this delay, the
status "Intermediate" is activated.
Maximum
Close
command
pulse
length
0.02…500.00
s
0.02
s
0.2 s
Determines the maximum length for a Close pulse from the output relay to the
controlled object. If the object operates faster than this set time, the control
pulse is reset and a status change is detected.
Maximum
Open
command
pulse
length
0.02…500.00
s
0.02
s
0.2 s
Determines the maximum length for a Open pulse from the output relay to the
controlled object. If the object operates faster than this set time, the control
pulse is reset and a status change is detected.
Control
termination
timeout
0.02…500.00
s
0.02
s
10 s
Determines the control pulse termination timeout. If the object has not
changed it status in this given time the function will issue error event and the
control is ended. This parameter is common for both open and close
commands.
Final trip
pulse
length
0.00…500.00
s
0.02
s
0.2 s
Determines the length of the final trip pulse length. When the object has
executed the final trip, this signal activates. If set to 0 s, the signal is
continuous. If auto-recloser function controls the object, "final trip" signal is
activated only when there are no automatic reclosings expected after opening
the breaker.
A
AQ
Q-C215
-C215
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00040
211
Содержание AQ-C215
Страница 1: ...AQ C215 Capacitor bank protection IED Instruction manual ...
Страница 2: ......
Страница 297: ...Figure 7 4 179 Example block scheme A AQ Q C215 C215 Instruction manual Version 2 07 Arcteq Relays Ltd IM00040 295 ...
Страница 318: ...Figure 8 14 200 Device installation A AQ Q C215 C215 Instruction manual Version 2 07 316 Arcteq Relays Ltd IM00040 ...
Страница 347: ...10 Ordering information A AQ Q C215 C215 Instruction manual Version 2 07 Arcteq Relays Ltd IM00040 345 ...