Programming
99
MVP-5200i Modero® ViewPoint® Touch Panel with Intercom - Instruction Manual
Button Commands (Cont.)
^BSP
Set the button size and its position on the page.
Syntax:
"'^BSP-<vt addr range>,<left>,<top>,<right>,<bottom>'"
Variable:
variable text address range = 1 - 4000.
left = left side of page.
top = top of page.
right = right side of page.
bottom = bottom of page.
Example:
SEND_COMMAND Panel,"'^BSP-530,left,top'"
Sets the button with variable text 530 in the left side top of page.
^BSM
Submit text for text area buttons. This command causes the text areas to send their text as strings to the NetLinx Master.
Syntax:
"'^BSM-<vt addr range>'"
Variable:
variable text address range = 1 - 4000.
Example:
SEND_COMMAND Panel,"'^BSM-500'"
Submits the text of the text area button.
^BSO
Set the sound played when a button is pressed. If the sound name is blank the sound is then cleared. If the sound name is not
matched, the button sound is not changed.
Syntax:
"'^BSO-<vt addr range>,<button states range>,<sound name>'"
Variable:
variable text address range = 1 - 4000.
button states range = 1 - 256 for multi-state buttons (0 = All states, for General buttons 1 = Off state and 2 = On state).
sound name = (
blank
- sound cleared,
not matched
- button sound not changed).
Example:
SEND_COMMAND Panel,"'^BSO-500,1&2,music.wav'"
Assigns the sound 'music.wav' to the button Off/On states.
^BVL
Log-On/Log-Off the computer control connection.
Syntax:
"'^BVL-<vt addr range>,<connection>'"
Variable:
variable text address range = 1 - 4000.
connection = 0 (Log-Off connection) and 1 (Log-On connection).
Example:
SEND_COMMAND Panel,"'^BVL-500,0'"
Logs-off the computer control connection of the button.
^BVN
Set the computer control remote host for the specified address.
Syntax:
SEND_COMMAND <DEV>,"'^BVN-<vt addr range>,<remote host>'"
Variables:
variable text address range = 1 - 4000.
remote host = 1 - 50 ASCII characters.
Example:
SEND_COMMAND Panel,"'^BVN-500,191.191.191.191'"
Sets the remote host to '191.191.191.191' for the specific computer control button.
^BVP
Set the network password for the specified address.
Syntax:
"'^BVP-<vt addr range>,<network password>'"
Variable:
variable text address range = 1 - 4000.
network password = 1 - 50 ASCII characters.
Example:
SEND_COMMAND Panel,"'^BVP-500,PCLOCK'"
Sets the password to PCLOCK for the specific PC control button.