57
HT 6Split
HT 12Split
Chapter 9 |
Control
IMPORTANT
The change log is saved at restart and remains un-
changed after factory setting.
CAUTION
There must be a heating or hot water demand to start
the compressor.
CAUTION
Do not start the compressor too often within a short
period of time, as this could damage the compressor
and accessories.
Menu 5.8 - Quick Start
It is possible to start the compressor from here.
Menu 5.9 - Underfloor drying function
Length period 1 – 7
Setting range: 0 – 30 days
Factory setting, period 1 – 3, 5 – 7: 2days
Factory setting, period 4: 3 days
Temp. period 1 – 7
Setting range: 15 – 65°C
Factory setting:
Activated: deactivated
period 1 20°C
period 2 30°C
period 3 40°C
period 4 45°C
period 5 40°C
period 6 30°C
period 7 20°C
Set the function for underfloor drying here.
You can set up to seven time periods with different
calculated supply flow temperatures. If less than sev
-
en periods are to be used, set the remaining time pe-
riods to 0 days.
Select the active window to activate the underfloor
drying function. A counter at the bottom shows the
number of days the function has been active.
Menu 5.11.1.2 - Charge pump (GP12)
Operating mode
Heating/cooling operation
Setting range: auto / intermittent
Factory settings: auto
Speed during operation
Heating, hot water, pool, cooling operation
Setting range: auto / manual
Factory settings: auto
Set the operating mode for the feed pump here.
Auto:
The feed pump runs according to the current
operating mode of the controller.
Intermittent:
The feed pump starts and stops 20 sec-
onds before and after the compressor in the heat pump.
Factory setting:
Menu 5.10 - Changes log
Menu 5.11 - Slave device settings
Menu 5.11.1 - EB101 - 5.11.8 - EB108
Read off any previous changes to the control system
here. The date, time and ID no. (unique to certain set-
tings) and the new set point value is shown for every
change.
Settings for installed slave devices can be entered in
the submenus.
Enter the settings for the installed slave devices here.
Menu 5.11.1.1 - Heat pump
Input the settings for the installed slave device here.
To view the available settings, see installation manual
for the relevant installed slave device.
Menu 5.7 - Start guide
When the HT 6Split / HT 12Split controller is started
up for the first time, the start guide is automatically
launched. In this menu, you have the option to start
it manually. See page 38 for more information about
the start guide.
ADVICE
If the “add. heat only” operating mode is to be used,
select it in menu 4.2.