Connection between
HT 6Split / HT 12Split and LSplit
The conductor connecting the devices must be con-
nected to the power supply clamp (TB) at LSplit and
to clamp (X10) at HT 6Split / HT 12Split .
Connect the phase (brown), neutral conductor (blue),
communication (black and grey) i protective (yellow-
green) according to the drawing:
IMPORTANT
The LSplit module is to be grounded before connect-
ing the devices with a cable. The cabling must be fixed
in such a way so that the terminal block is not under
tension. The terminal without insulation is 8 mm long.
LSplit
Min.
5 x 2,5 mm
2
Chapter 6 |
Electrical connections
Connection of the external temperature
sensor
5
4
3
2
1
SHK 200S/ SHK 200S-6
BT1
BT1
AA3-X6
The outdoor temperature sensor (included in the kit)
should be connected to the HT 6Split / HT 12Split unit
on the AA3-X6:1 and AA3-X6:2.
HT 6Split / HT 12Split
L Split
HT 6Split /
HT 12Split
X10
When many power consumers are connected in the
property at the same time as the electric additional
heat is in operation, there is a risk of the property’s
main fuses tripping. Control module has an integrat-
ed load monitor that controls the power steps for the
electric additional heat by disconnecting step by step
in event of overload in a phase. Reconnection occurs
when other current consumption is reduced.
A current sensor (BE1 - BE3) must be installed on
each incoming phase conductor into the electrical
distribution unit, to measure the current. The electri-
cal distribution unit is an appropriate installation point.
Connect the current sensors to a multi-core cable in
an enclosure next to the electrical distribution unit.
Use unscreened multi-core cable of at least 0.5 mm²,
from the enclosure to control module.
Connect the cable to the input board (AA3) on termi
-
nal block X4:1-4 where X4:1 is the common terminal
block for the three current sensors.
The value for the size of the fuse is set in menu 5.1.12
to correspond with the size of the property’s main
fuse. Here it is also possible to adjust the current
sensor’s transformer ratio. Enclosed current sensors
have a transformer ratio of 300 and, if these are used,
the incoming current must not exceed 50 A.
If the installed heat pump is frequency controlled, it
will be limited when all power stages are disengaged.
Optional connections
LOAD MONITOR
Connecting current sensors
IMPORTANT
The voltage from the current sensor to the input
board must not exceed 3.2 V.
N
E
P
L
1
L
2
L
3
E
lectrical distribution
unit
C
ontrol module
I
ncoming electricity
L N
1
1
0
2 3 4
PE
1 2 3
4
LEK
SMO
E
xternt
E
xternal
C
ontrol module
BE3
BE2
BE1
AA3
-
X4
L N
1
1
0
2 3 4
PE
1 2 3
4
LEK
AA3
-
X4
1
2
3
4
5
6