HT 6Split
HT 12Split
5 Outdoor unit LSplit
Transport and storage
Assembly
Lift from the street to the set up
location
LSplit must be transported and stored vertically.
Do not place LSplit directly on the lawn or other non
solid surface.
If there is a risk of snow slip from roof, a protective
roof or cover must be erected to protect the heat
pump,pipes and wiring.
If the base allows, the simplest thing is to use a pallet
truck to move the LSplit to the set up location.
If LSplit needs to be transported across soft ground,-
such as a lawn, we recommend that a crane truck is
used that can lift the unit to the installation location.
When LSplit is lifted with a crane, the packaging must
be undamaged and the load distributed with a boom,-
see the illustration above.
If a crane cannot be used LSplit can be transported
using an extended sack truck. LSplit must be used
on the side marked "heavy side" and two people are
required to get the LSplit up.
•
Place LSplit outdoors on a solid level base that
can take the weight, preferably a concrete foun-
dation. If concrete slabs are used they must rest
on asphalt or shingle.
•
The concrete foundation or slabs must be posi-
tioned so that the lower edge of the evaporator
is at the level of the average local snow depth;
however, a minimum of 300 mm. Stands and at-
tachments on the page are available in the LSplit
instruction in the "Accessories" chapter.
•
LSplit should not be positioned next to noise sen-
sitive walls, for example, next to a bedroom.
•
Also ensure that the placement does not incon
-
venience the neighbours.
•
LSplit must not be placed so that recirculation of
the outdoor air can occur. This causes lower out-
put and impaired efficiency.
•
The evaporator should be sheltered from direct
wind, which negatively affects the defrosting
function. Place LSplit protected from wind against
the evaporator
•
Large amounts of condensation water, as well
as melt water from defrosting, can be produced.
Condensation water must be led off to a drain or
similar (see page13).
•
Care must be exercised so that the heat pump is
not scratched during installation.
IMPORTANT
Ensure that the heat pump cannot fall over during trans-
port.
IMPORTANT
The centre of gravity is offset to one side (seep print on
the packaging).
LEK
XX mm
300 mm
Chapter 5 |
Outdoor unit LSplit