12
HT 6Split
HT 12Split
Indoor HT 6Split / HT 12Split module
•
It is recommended that the HT 6Split / HT 12Split
module should be installed in a room with a floor
drain, at best in a utility room or a boiler house.
•
The floor must be solid, concrete at best.
•
The HT 6Split / HT 12Split module must be set
with its back to the outer wall, at best in a room
where noise is not a problem. If possible, do not
place the device near a wall of a bedroom or an-
other room where noise might be a problem.
•
The device can be leveled using regulated legs.
•
Pipes must be led in such a way that they are not
adjacent to the bedroom or living room.
•
Remember to leave about 800 mm free space at
the front and 220 mm over the device to provide
for future maintenance.
1. Connect HT 6Split / HT 12Split module to the
heating system, cold, and hot water pipelines.
2. Install the cooling medium pipes.
3. Connect the outdoor temperature sensor, and ca-
bles between HT 6Split / HT 12Split and LSplit.
4. Connect power supply to module HT 6Split / HT
12Split.
5. Proceed according to start-up instructions in
chapter Start-up and regulation.
Recommended order of assembly
P
SHK 200S
SHK 200S-6
XL10
XL18
XL19
XL1
XL2
-EB101
-BT1
HS1 -BP4
-BT15
-BT3
-GP12
-BT64
-BT25
-QN12
-BT63
-BT71
-QN10
-BT7
-BT6
P
Scheme with the connection of an additional heat source
Chapter 4 |
Pipe connections
HT 6Split
HT 12Split