Benchmark 2500 - 3000 Boilers
CHAPTER 6 – SAFETY DEVICE TESTING
OMM-0094_0F
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
75
of
207
GF-137
Ph.: 800-526-0288
09/30/2015
Low Gas Pressure Fault Test
1. Remove the
1/4"
plug from the ball valve at the Low Gas Pressure switch shown in the
lower portion of Figure 6-1a and 6-1b.
2. Install a
0 – 16“ W.C. (0 – 4000 Pa)
manometer or a W.C. gauge where the
where the
1/4"
plug was removed.
3. Slowly open the ball valve near the Low Gas Pressure switch.
4. Place the unit in MANUAL mode and adjust the Air/Fuel Valve position (% open)
between 25 and 30%
.
5. While the unit is firing, slowly close the external manual gas shut-off valve.
6. The unit should shut down and display a
GAS PRESSURE
fault message at
approximately:
3.6” W.C. (897 Pa) for BMK 2500
and
2.6” W.C. (648 Pa) for BMK
3000
.
7. Fully open the external manual gas shut-off valve and press the
CLEAR
button on the
Control Box.
8. The fault message should clear and the
FAULT
indicator should go off. The unit should
restart.
9. Upon test completion, close the ball valve and remove the manometer. Replace the
1/4"
plug removed in step 1.
6.3 HIGH GAS PRESSURE TEST
To simulate a high gas pressure fault, refer to Figure 6-2a and 6-2b and perform the following
steps:
Figure 6-2a:
BMK 2500:
High Gas Pressure Fault Test
SSOV
TO
AIR/FUEL
VALVE
HIGH GAS
PRESSURE
SWITCH
LOW GAS
PRESSURE
SWITCH
MANUAL
SHUT-OFF
VALVE
HIGH GAS
BALL VALVE
NATURAL
GAS INLET
1/4” NPT PLUG
And Ball Valve
(install manometer
here for HIGH GAS
PRESSURE FAULT
TEST