Benchmark 2500 - 3000 Boilers
CHAPTER 9. BOILER SEQUENCING TECHNOLOGY
OMM-0094_0F
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
131
of
207
GF-137
Ph.: 800-526-0288
09/30/2015
Option 5 – Continued
Step 3: Configure ALL C-More Units
On ALL Boilers:
1. Go to the
Configuration
menu
item and set the
BST Menu
item to
Enabled
.
2. Go to the
Boiler Sequencing Menu
item
and set the
BST Mode
item to
BST Slave
(for now).
On MASTER only:
3. Go to the
BST Setpoint
item and enter the Failsafe Setpoint.
4. Go to the
BST Setup Menu
item and set to
Enabled
.
5. Go to the
BST Setpoint Mode
item and select
Remote Setpoint
.
6. Go to the
Head Temp Source
item
and select
FFWD Temp
.
7. Go to the
BST Remote Signal
and select either
4-20ma
or
0-20ma
.
When ALL C-More units have been configured
:
8. Go to the
Boiler Sequencing Menu
item
of the desired Master
unit
and set the
BST Mode
item to
BST MASTER
.