Benchmark 2500 - 3000 Boilers
CHAPTER 8 – TROUBLESHOOTING GUIDE
OMM-0094_0F
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
113
of
207
GF-137
Ph.: 800-526-0288
09/30/2015
TABLE 8-1: BOILER TROUBLESHOOTING – Continued
FAULT INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
INTERLOCK
OPEN
1.
Interlock jumper not installed or
removed.
2.
Energy Management System
does not have unit enabled.
3.
Device proving switch hooked to
interlocks is not closed.
1.
Check for a jumper properly installed across the interlock terminals in
the I/O box.
2.
If there are two external wires on these terminals check any Energy
Management system to see if they have the units disabled (a jumper
may be temporarily installed to see if the interlock circuit is functioning).
3.
Check that proving switch for any device hooked to the interlock circuit
is closing and that the device is operational.
LINE VOLTAGE
OUT OF PHASE
1.
Line and Neutral switched in AC
Power Box.
2.
Incorrect power supply
transformer wiring.
1.
Check hot and neutral in AC Power Box to ensure they are not
reversed.
2.
Check transformer wiring, in AC Power Box, against the power box
transformer wiring diagram to ensure it is wired correctly.
LOW GAS
PRESSURE
1.
Incorrect supply gas pressure.
2.
Defective
Low Pressure Gas
switch.
1.
Measure gas pressure upstream of the SSOV Actuator(s) with the unit
firing. For FM gas trains, ensure it is
between 4.0” W.C. and 14” W.C.
(996 and 3487 Pa)
. For DBB gas trains, ensure it is between
4.5" W.C.
and 14” W.C.
(1121 and 3487 Pa)
(see section 4.3).
2.
Measure gas pressure at the Low Gas Pressure switch. If it is
greater
than
3.6” W.C. (897 Pa)
for BMK 2500 or
2.6” W.C. (648 Pa)
for BMK
3000, measure continuity across the switch and replace if necessary.
LOW WATER
LEVEL
1.
Insufficient water level in system.
2.
Defective water level circuitry.
3.
Defective water level probe.
1.
Check system for sufficient water level.
2.
Test water level circuitry using the Control Box front panel
LOW
WATER TEST
and
RESET
buttons. Replace water level circuitry if it
does not respond.
3.
Check continuity of probe end to the shell, change probe if there is no
continuity.
MODBUS
COMMFAULT
Unit not seeing information from
Modbus network.
Check network connections. If fault persists, contact qualified Service
Personnel.
PRG SWTCH CLOSED
DURING IGNITION
1.
A/F Valve rotated open to purge
and did not rotate to ignition
position.
1.
Start the unit. The Air/Fuel Valve should rotate to the purge (open)
position, then back to ignition position (towards closed) during the
ignition cycle. If the valve does not rotate back to the ignition position,
check the Air/Fuel Valve calibration. If calibration is okay, the problem
may be in the Air/Fuel Valve or the Control Box. Refer fault to qualified
service personnel.