Benchmark 2500 - 3000 Boilers
CHAPTER 2 – INSTALLATION
OMM-0094_0F
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
29
of
207
GF-137
Ph.: 800-526-0288
09/30/2015
2.10.7 SHIELD Terminals
The SHIELD terminals are used to terminate any shields used on sensor wires connected to the
unit. Shields must only be connected to these terminals.
2.10.8 ANALOG OUT Terminals
The ANALOG OUT terminals (+ & -) output from 0 to 20 mA and may be used to monitor
Setpoint, Outlet Temperature, Valve Position 4-20 mA, Valve Position 0-10v or be set to OFF.
Default setting in the C-More controller is Valve Position 0-10v and settings behave as follows:
1. When 0-10VDC is selected, the voltage output is used by the controller to modulate the
combustion blower via the I/O Box terminals labeled VFD/Blower (Section 2.10.11).
2. If On Board Boiler Sequencing Technology (BST) is enabled, the Analog Output
terminals are used to drive the isolation valve, open and closed.
NOTE
When driving an isolation valve, shorting jumper #JP2 on the I/O Board
MUST
be installed.
3. When the 4-20mA is selected for the Analog Output, the 0-10VDC is disabled at the
VFD/Blower terminals, and the selected output is available at the terminals labeled
Analog /-.
2.10.9 RS485 Comm Terminals
The RS-485 communication terminals (+, GND, & -) are used when the boiler plant is being
controlled by an Energy Management System (EMS) or AERCO ACS (formerly BMS/BMS-II)
using Modbus (RS-485) communication.
2.10.10 RS232 Comm Terminals
As of Firmware version 4.0 and above, these terminals are used only by factory-trained
personnel to monitor OnAER communications via a portable computer.
2.10.11 VFD/BLOWER Terminals
These terminals (0-10 & AGND) send an analog signal to control the blower speed. When any
of the 4-20mA options is selected for the Analog Outputs (Section 2.10.8), the output from the
VFD/Blower terminals is disabled.
2.10.12 Interlock Terminals
The unit offers two interlock circuits for interfacing with Energy Management Systems and
auxiliary equipment such as pumps or louvers or other accessories. These interlocks are called
the Remote Interlock and Delayed Interlock (REMOTE INTL’K IN and DELAYED INTL’K IN in
Figure 2-12). Both interlocks, described below, are factory wired in the closed position (using
jumpers).
NOTE
Both the Delayed Interlock and Remote Interlock must be in the
closed position for the unit to fire.
2.10.12.1
Remote Interlock In (OUT & IN)
The remote interlock circuit is provided to remotely start (enable) and stop (disable) the unit
if desired. The circuit is 24 VAC and comes factory pre-wired closed (jumped).