Benchmark 2500 - 3000 Boilers
CHAPTER 3 – OPERATION
Page
44
of
207
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0094_0F
09/30/2015
Ph.: 800-526-0288
GF-137
Table 3-4: Configuration Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
21
Setpt Limit Band
0°F (0
°
C)
10°F (5.5
°
C)
5°F (2.75
°
C)
22
Network Timeout
5 sec.
999 sec.
30 sec.
23
Shutoff Dly Temp
0°F (0
°
C)
25°F (13.75
°
C)
10°F (5.5
°
C)
24
Demand Offset
0°F (0
°
C)
25°F (13.75
°
C)
0°F (0
°
C)
25
Deadband High
0°F (0
°
C)
25°F (13.75
°
C)
5°F (2.75
°
C)
26
Deadband Low
0°F (0
°
C)
25°F (13.75
°
C)
5°F (2.75
°
C)
27
IGST Version
V2.00 or Lower
V2.02
28
IGN Time Setting
4 sec.
7 sec.
29
Slow Shutdown
Enabled or Disabled
Disabled
30
Slow Sht Duration
0 sec.
9,999 sec.
60 sec.
31
Slow Sht Threshold
40%
100%
60%
32
BST Menu
Enabled or Disabled
Disabled
*NOTE
The
Bldg Ref Temp
and
Reset Ratio
menu Items are only
displayed when the
Outdoor Sensor
menu item is set to
Enabled
.
CAUTION
DO NOT
change
the
Analog Output
menu item from its default
setting (Valve Position 0-10V).
3.7 TUNING MENU
The
Tuning
menu items in Table 3-5 are Factory set for each individual unit. Do not change
these menu entries unless specifically requested to do so by factory-trained personnel.
Table 3-5: Tuning Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
1
Prop Band
1°F (-17.2
°
C)
120°F (48.9
°
C)
70°F (21.1
°
C)
2
Integral Gain
0.00
2.00
1.00
3
Derivative Time
0.0 min
2.00 min
0.0min
4
Warmup Prop Band
1°F (-17.2
°
C)
120°F (48.9
°
C)
95 °F (35
°
C)
5
Warmup Int Gain
0.00
2.00
0.50
6
Warmup PID timer
0 sec.
240 sec.
20 sec.
7
Reset Defaults?
Yes, No, Are You Sure?
No