Benchmark 2500 - 3000 Boilers
CHAPTER 9. BOILER SEQUENCING TECHNOLOGY
Page
134
of
207
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0094_0F
09/30/2015
Ph.: 800-526-0288
GF-137
Option 7 –
Continued
Step 3: Configure ALL C-More Units
On ALL Boilers:
1. Go to the
Configuration
menu
item
and set the
BST Menu
item to
Enabled
.
2. Go to the
Boiler Sequencing Menu
item
and set the
BST Mode
item to
BST Slave
(for now).
On MASTER only:
3. Go to the
BST Setpoint
item and enter the Failsafe Setpoint.
4. Go to the
BST Setup Menu
item and set to
Enabled
.
5. Go to the
BST Setpoint Mode
item and select Remote
Setpoint
.
6. Go to the
BST Remote Signal
and select either
4-20ma
or
0-20ma
.
7.
Go to the
Head Temp Source
item and select
Network
.
8. Go to the
Header Temp Addr
item and
enter the Modbus Address (240).
9. Go to the
Header Temp Point
item and enter the Modbus Point (14).
When ALL C-More units have been configured:
10. Go to the
Boiler Sequencing Menu
item
of the desired Master
unit
and set the
BST Mode
item to
BST MASTER
.