BMK 3000 Natural Gas Combustion Calibration
–
Continued
16. Once the oxygen level is within the specified range at 100%, record the O
2
, NOx and CO
readings on the Combustion Calibration Data Sheets provided with the unit.
17.
Lower the valve position to 70% using the ▼arrow key.
NOTE
The remaining combustion calibration steps are performed using
the
Combustion Cal
menu
included in the C-More Control System.
The combustion calibration control functions will be used to adjust
the oxygen level (%) at valve positions of 70%, 50%, 40%, 30%
and 14% as described in the following steps. These steps assume
that the inlet air temperature is
within the range of 50°F to 100°F
(10.0°C to 37.8°C)
. If NOx readings exceed the target values
shown, increase the O
2
level up to 1% higher than the listed
calibration range. Record the increased O
2
value on the
Combustion Calibration sheet.
18. Press the
MENU
key on the front panel of the C-More and access the
Setup
menu. Enter
password 6817 and then press the
ENTER
key.
19. Press the
MENU
key on the front panel of the C-More until
Combustion Cal Menu
appears on the display.
20.
Press the ▲ arrow key until
SET Valve Position
appears on the display.
21. Press the
CHANGE
key.
SET Valve Position
will begin to flash.
22.
Press the ▲ arrow key until the
SET Valve Position
reads
70%
. Press the
ENTER
key.
23.
Next, press the down (▼) arrow key until
CAL Voltage 70%
is displayed.
24. Press the
CHANGE
key and observe that
CAL Voltage 70%
is flashing.
25. The oxygen level at the 70% valve position should be as shown below. Also, ensure that
the nitrogen oxide (NOx) and carbon monoxide (CO) readings do not exceed the
following values:
Table 4-6:
Combustion Calibration Readings – 70% Valve Position
Valve Position
Oxygen (O
2
) %
Nitrogen Oxide (NOx)
Carbon Monoxide (CO)
70%
4.5% - 5.6%
≤
20 ppm
<100 ppm
26.
If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the ▲ arrow key increases the oxygen level and pressing the down ▼
arrow key decreases the oxygen level.
27. Once the oxygen level is within the specified range at 70%, press the
ENTER
key to
store the selected blower output voltage for the 70% valve position. Record all readings
on the Combustion Calibration Sheets provided.
28. Repeat steps 20 through 27 for valve positions of 70%, 50%, 40%, 30% and 14%. The
oxygen (O
2
), nitrogen oxide (NOx) and carbon monoxide (CO) should remain within the
same limits for all valve positions as shown in the following table.