Benchmark 2500 - 3000 Boilers
CHAPTER 3 – OPERATION
OMM-0094_0F
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
43
of
207
GF-137
Ph.: 800-526-0288
09/30/2015
Table 3-4: Configuration Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
1
Internal Setpt
Lo Temp Limit
Hi Temp Limit
130°F (54.4°C)
2
Unit Type
KC Boiler, KC Boiler LN,
BMK Blr Std, BMK Blr Std Dual,
BMK Blr LN, BMK Blr LN Dual
KC Water Heater,
KC Water Heater LN, RECON Wtr
Heater, Innovation WH
BMK Boiler LN
3
Unit Size
(Only the unit sizes
available for the Unit
Type will be displayed)
2500 MBH (733 Pa)
3000 MBH (879 Pa)
2500 MBH (733 Pa)
or
3000 MBH (879 Pa)
4
Fuel Type
Natural Gas or Propane
Natural Gas
5
Boiler Mode
Constant Setpoint,
Remote Setpoint,
Direct Drive, Combination,
Outdoor Reset
Constant Setpoint
6
Remote Signal
(If Mode = Remote
Setpoint, Direct Drive or
Combination)
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
PWM Input (Legacy BMS), Network
4 – 20 mA,
1-5V
7
* Bldg Ref Temp
(If Mode = Outdoor
Reset)
40°F
(4.4
°
C)
230°F
(110
°
C)
70°F
(21.1
°
C)
8
* Reset Ratio
(If Mode = Outdoor
Reset)
0.1
9.9
1.2
9
Outdoor Sensor
Enabled or Disabled
Disabled
10
* System Start Tmp
(If Outdoor Sensor =
Enabled)
30°F
(-1.1
°
C)
100°F
(37.8
°
C)
60°F
(15.6
°
C)
11
Setpt Lo Limit
40°F (4.4
°
C)
Setpt Hi Limit
60°F (15.6
°
C)
12
Setpt Hi Limit
Setpt Lo Limit
210°F (98.9
°
C)
195°F (90.6
°
C)
13
Temp Hi Limit
40°F (4.4
°
C)
210°F (98.9
°
C)
195°F (90.6
°
C)
14
Max Valve Position
40%
100%
100%
15
Pump Delay Timer
0 min.
30 min.
0 min.
16
Aux Start On Dly
0 sec.
120 sec.
0 sec.
17
Failsafe Mode
Shutdown or Constant Setpt
Shutdown
18
Analog Output
Off, Setpoint, Outlet Temp, Valve
Pos 4-20mA, valve Pos 0-10v
Valve Pos 0-10v
19
Low Fire Timer
2 sec.
600 sec.
2 sec.
20
Setpt Limiting
Enabled or Disabled
Disabled