Benchmark 2500 - 3000 Boilers
CHAPTER 3 – OPERATION
OMM-0094_0F
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
41
of
207
GF-137
Ph.: 800-526-0288
09/30/2015
3.4 OPERATING MENU
The
Operating
menu displays a number of key operating parameters for the unit as listed in
Table 3-2. This menu is “Read-Only” and does not allow personnel to change or adjust any
displayed items. Since this menu is “Read-Only”, it can be viewed at any time without entering a
password. Pressing the
▲ arrow key to display the menu items in the order listed (Top-Down).
Pressing the
▼ arrow key will display the menu items in reverse order (Bottom-Up).
Table 3-2: Operating Menu
Menu Item Display
Available Choices or Limits
Minimum
Maximum
1
Active Setpoint
40°F (4.4
°
C)
240°F (116
°
C)
2
Inlet Temp
40°F (4.4
°
C)
140°F (60
°
C)
3
Air Temp
-70°F (-56.7
°
C)
245°F (118
°
C)
4
* Outdoor Temp
-70°F (-56.7
°
C)
130°F (54.4
°
C)
5
Valve Position In
0%
100%
6
* Valve Position Out
0%
100%
7
Exhaust Temp
°F
°F
8
Flame Strength
0%
100%
9
Oxygen Level
0%
21%
10
Ignition Time
0.00
10.00
11
SSOV Time to OPN
0.00
10.00
12
Spark Current
0
2.5 A
13
Run Cycles
0
999,999,999
14
Run Hours
0
999,999,999
15
Fault Log
0
19
*NOTE
The Outdoor Temp and Valve Position Out display items shown
with an asterisk in Table 3-2 will not be displayed unless the
Outdoor Sensor function has been enabled in the
Configuration
menu (Table 3-4).
3.5 SETUP MENU
The
Setup
menu (Table 3-3) permits the operator to enter the unit password (159) which is
required to change the menu options. To prevent unauthorized use, the password will time-out
after 1 hour. Therefore, the correct password must be reentered when required. In addition to
permitting password entries, the
Setup
menu is also used to enter date and time, and units of
temperature measurements. A view-only software version display is also provided to indicate
the current Control Box software version.