Benchmark 2500 - 3000 Boilers
CHAPTER 4 – INITIAL START-UP
Page
64
of
207
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0094_0F
09/30/2015
Ph.: 800-526-0288
GF-137
Table 4-8: Over-Temperature
Alarm Switch Controls and Display
CONTROL OR
DISPLAY
MEANING
FUNCTION
LED Display
TEMP status
Displays current water temperature or setpoint.
RST
RESET Button
Resets the unit after an alarm condition.
UP Button
Increases the displayed temperature.
DOWN Button
Decreases the displayed temperature.
SET
SET Button
Used to access and store parameters in the unit.
Perform the following steps to check or adjust the
Over-Temperature Alarm
switch settings:
Switch Check or Adjustment
1.
Set the
ON/OFF
to the ON position.
2.
Press the
SET
button on the
Over-Temperature Alarm
switch.
SP
will appear in the
display.
3.
Press the
SET
button again. The current over-temperature limit value stored in memory will
be displayed.
(Default = 210°F, 98.9
°C
)
4.
If the display does not show the required over-
temperature alarm setting, press the ▲ or
▼ arrow button to change the display to the desired temperature setting.
5.
Once the desired over-temperature alarm setting (210ºF) is displayed, press the
SET
button to store the setting in memory.
6.
To calibrate the offset (P1), press and hold the
SET
button for 8 seconds on the
Over-
Temperature Alarm
switch. Access code value 0 should appear in the display. The switch
comes from the factory with the code set at 0. AERCO recommends that you do not
change this code.
7.
Press the
SET
button again to enter the code. The first parameter label (
SP
) will appear in
the display.
8.
Using the ▲ and ▼ arrow keys, select parameter P1.
9.
Press
SET
to view the value stored in memory.
10.
If the desired value is not displayed, modify the setting using the ▲ and ▼ arrow keys.
The value can be changed from -10° to +10°
(-5.5
°C
to + 5.5
°C)
offset. Press
SET
to
enter the value and exit to the text parameter.
11.
To exit the programming mode, press the
SET
and ▼ buttons simultaneously, or simply
wait one minute and the display will automatically exit the programming mode.
12.
Once the programming mode has been exited, the display will show the current outlet
water temperature of the boiler.