Benchmark 2500 - 3000 Boilers
CHAPTER 3 – OPERATION
OMM-0094_0F
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
51
of
207
GF-137
Ph.: 800-526-0288
09/30/2015
Figure 3-6: Air/Fuel Valve In Ignition Position
6.
Up to 4 seconds will be allowed for ignition to be detected. The igniter relay will be
turned off one second after flame is detected.
7.
After 2 seconds of continuous flame,
FLAME PROVEN
will be displayed and the flame
strength will be indicated. After 5 seconds, the current date and time will be displayed
in place of the flame strength.
8.
With the unit firing properly, it will be controlled by the temperature controller circuitry.
The boiler’s
VALVE POSITION
will be continuously displayed on the front panel
bargraph.
Once the demand for heat has been satisfied, the Control Box will turn off the SSOV gas valve.
The blower relay will be deactivated and the Air/Fuel Valve will be closed.
STANDBY
will be
displayed.
TO BLOWER
AIR IN
IGNITION
VALVE POSITION
DIAL AT
25% to 35%
STEPPER
MOTOR