Section 10 – Access Control
10-11
DS2
RXD
DS1
TXD
RS485
E2
E3
E4
E5
E6
E7
E8
E9
TERMINAL STRIP TB1
FOR RS-485 BUS
CONNECTIONS
JUMPER E1
(REMOVE JUMPER TO
DISCONNECT RS-485
TERMINATING RESISTOR)
GND
+ 12V
COM
COM +
(BLK) 1
(YEL) 3
(RED) 2
(BLU) 4
E1
TB3
BATTERY
1
2 +
1
2 +
3 "0"
4 "1"
5 "A"
6 "B"
CUT R8
TB2
BATTERY AREA
12V, O.8AH
TB1
E10
E11
+
C5
D4
D5
D7
D6
D8
D10
C7
C6
C3
C4
U2
U1
D2
R7
D3
R8
D1
D11
Figure 10-4: Modifying ACIU for Operation with Dorado 7401 or 7901 Card Reader
Using the Operating Panel for Access Control
Access can be controlled not only by card/key readers, but also by the FOCUS operating panel. The
person requesting access must enter a valid 6-digit code to gain entry. Either of three methods can be
used:
•
Using an ACIU to control power to a 12-volt door strike.
The control unit commands the ACIU to have its on-board battery provide the 12V potential for
releasing the door strike when a valid code is entered at the operating panel. No connection is
required between the operating panel and the ACIU. The only ACIU connections that are needed
are to the RS-485 bus and to the door strike. The operating panel is linked to the ACIU through
programming.
•
Sharing an ACIU with a card/key reader.
An operating panel is linked to the same ACIU as a card/key reader, so that either the card/key
reader or the operating panel can be used for access control. In this arrangement, a person who
forgot his card can use the operating panel to gain access. Note that the operating panel can only
be installed indoors.
•
Using a BA Access output point to control the power to the strike.
The control unit commands the BA Access output point to turn on when a valid code is entered at
the operating panel. When turned on, the BA Access output point closes the circuit to a separate
power source, thereby applying power to the door strike.
Installing the Operating Panel for Use With Access Control
If an operating panel is being used for access control, it must be assigned to communication Group 0.
Install the operating panel in the usual manner.
Where an operating panel is being used for access control with an ACIU, its communication Unit number on
the RS-485 bus must coincide with the communication Unit number of the ACIU. An operating panel being
used for access control (Communication Group 0) becomes locked out during the period that any other
operating panel at communication Group 0 becomes activated, and vice versa.
Содержание Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Страница 2: ......
Страница 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Страница 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Страница 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Страница 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Страница 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Страница 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Страница 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Страница 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Страница 210: ...Index Index 6...
Страница 214: ...A 4...
Страница 216: ...9 3l K3471V2 1 00 ADT Security Services Inc One Town Center Road Boca Raton FL 33486 Copyright 1999...