Section 5 - Gateways
5-21
BLACK
RED
YELLOW
BLUE
X
X
X
X
BLK
RED
YEL
BLU
ORA
BLU/WHT
WHT
RED/WHT
BLK/WHT
X
X
X
X
X
869706 (10K 5% 1/2W)
WHT
BLU/WHT
RED
BLK
BLU/GRN
GRN
X
ORA
BLU/ORA
YEL
BLU/YEL
472366
SIM
247650
4W/2W
ADAPTER
BOARD
(8mA NORMAL
STANDBY)
(35mA ALARM)
10.2 - 13.8VDC
SUPERVISED
4Ma NORMAL STANDBY
30Ma MAX WHEN ALL DEVICES IN ALARM
244708
3K EOLR
(INSIDE ELECTRICALLY
LAST DEVICE IN LOOP)
10K 5% 1/2W
REMOVE
JUMPER J1
Figure 5-12: SIM Connections to a 4-Wire/2-Wire Adapter
Compatible Detectors for 4-Wire/2-Wire Adapter
Spot-Type Detector
UL ID
Base
UL ID
429C; 429CT; 521B ESL Photoelectric
S10
---
521BXT Photo w/Thermostat
S10
---
429AT Photoelectric Head
S10A
435006 (3536-601)
S00
435008 (3536-612) Ionization Head
---
435006 (3536-601)
S00
435170 (3536-613) Heat Head
---
435006 (3536-601)
S00
Air-Duct Detector
Function Card
UL ID
435152 (3537-001) 611UD Photoelectric Head
435150 (3537-010) (609U10)
S00
435153 (3537-002) 612UD Ionization Head
435150 (3537-010) (609U10)
S00
When smoke and fire doors are held in the open position to allow free movement in corridors of
buildings, it is required that the doors be released when a fire alarm is activated. This requires a
472488 supervised SIM or 472366 SIM to release the Door Hold-Open device.
To install a 472488 supervised SIM or 472366 SIM to release the Door Hold-Open device, perform the
following steps:
Step
Action
1
Mount and connect the SIM device. See
Wiring a SIM or SIM Sensor
shown previously in this
section.
Note:
When 472366 SIM is used, the cable run between the SIM and Door Hold-Open device
can not exceed 3 feet.
2
Program it as FAC (21) point type.
For NFPA Life Safety applications, install a 472367 Door Contact to monitor the status of the door.
Program it as MID (5) point type.
Installing the Loop Interface Module (LIM) (472425)
The LIM connects to the trunk of a SIM gateway trunk and it functions like a SIM, but it employs a 2-
wire protection loop that is supervised for grounds. Consequently, it can be used for retrofit
applications involving sensors connected to a 2-wire loop, fire alarm applications that require a ground-
supervised loop, and other applications in which a SIM cannot be used for one reason or another.
Содержание Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Страница 2: ......
Страница 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Страница 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Страница 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Страница 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Страница 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Страница 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Страница 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Страница 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Страница 210: ...Index Index 6...
Страница 214: ...A 4...
Страница 216: ...9 3l K3471V2 1 00 ADT Security Services Inc One Town Center Road Boca Raton FL 33486 Copyright 1999...