Section 19 – System Operation
19-11
Option
Function
Entry Delay
This applies to installations where the operating panel for the BA group is
located inside of the protected area. The delay permits someone opening the
premises enough time to walk to the operating panel and turn the
protection to Day Set without creating an alarm. The delay starts when the
entrance door is opened and ends when the protection is turned off. The
sounder in the operating panel emits a steady tone during the delay period.
The delay time is selectable from 0 to 255 seconds, in 1-second increments.
UL
The entry delay, which is selectable in 1-second increments in the range of 1 to 255 seconds, must not
exceed 45 seconds for UL installations.
Option
Function
Exit Delay
This applies to installations where the operating panel for the BA group is
located inside of the protected area. The delay permits someone leaving the
premises at closing enough time to turn the protection to Nite Set and walk
to the exit door and close it, without creating an alarm. The delay time is
selectable from 0 to 255 seconds, in 1-second increments.
Exit Fail
This is used to make sure that someone exits the BA group after turning the
protection to Nite Set, and can only be used if the operating panel is located
inside of the protected area. An Exit Fail signal is transmitted to the CCC if
the customer turns the protection to Nite Set, but fails to trip a movable
delayed sensor in the exit path within the exit delay period.
One Exit
This causes the exit delay period for the respective BA group to end when a
movable delayed sensor is restored or the exit door is closed, after the BA
group is changed to Nite Set. This option can only be used where:
•
There is only one movable delayed sensor in the exit path, and the
customer will pass through that protection only once when exiting.
•
The customer has specifically requested it, and fully understands the
operation and false alarm potential that exists if someone wants to go
back for something they forgot after exiting.
One Open
Ordinarily, the BA group may be repeatedly turned on and off as long as it
is within the scheduled opening and closing time. This option permits only
one BA group on-to-off transition per schedule (maximum of 2 per day if two
schedules are used). This prevents someone from opening a BA group after
it has been closed until the next scheduled opening time is reached.
Off (2-Man Rule)
This prevents the BA protection for the selected BA group from being
turned off unless two valid ID codes are entered on the same operating
panel within 45 seconds. Once the BA group is off, the entry of any valid ID
code for the group will activate the operating panel.
Irregular Off (2-
Man Rule)
This option prevents the turning off of the selected BA group outside the
scheduled open window (e.g., re-opening the same day after the scheduled
closing, opening earlier than the scheduled opening, or opening on a day
that the BA group is not scheduled to be opened) unless two valid ID codes
are entered at the same operating panel within 45 seconds. Only one ID
code is needed to open inside of a schedule window.
BA Shed
This allows the control unit to shed BA protection for the BA group after 4
hours of AC power failure. This permits reserving the standby batteries for
FA devices to ensure 24 hours of FA standby time. The selective shedding
also allows preserving the BA protection for BA group with a vault or safe
by electing not to shed the protection for a power outage beyond 4 hours.
Содержание Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Страница 2: ......
Страница 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Страница 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Страница 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Страница 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Страница 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Страница 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Страница 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Страница 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Страница 210: ...Index Index 6...
Страница 214: ...A 4...
Страница 216: ...9 3l K3471V2 1 00 ADT Security Services Inc One Town Center Road Boca Raton FL 33486 Copyright 1999...