FOCUS 200 PLUS Installation and Setup Guide
10-8
Summary of Access Control Card/Key Readers
Access
Control
Device
Model
Card/Key
Type
Application
∗∗
User Operation
Card/Key
Programming
Reader DIP
Switch
Settings
ACIU
Strike
Voltage
Settings
Sensor
Engineering
Wiegand Card
Reader
3152540 Epic Three
LED
Wiegand Card
Indoor/Outdoor
Card swipe
None—card comes
pre-programmed
with site code and
user code.
None required
12-volt strike
(E11 = IN on
ACIU)
Motorola
Indala
Proximity Card
Reader
Slimline Proximity
Card Reader 4”
Range
WallSwitch
Proximity Card
Reader 4” Range
Proximity
Card
or
Proximity Key
Tag
Indoor/Outdoor
Card introduced within 4” of
reader
Key Tag introduced within
2.5” of reader
None—card comes
pre-programmed
with site code and
user code.
None required
12-volt strike
(E11 = IN on
ACIU)
Dorado Pass-
Through Card
Reader
∗
3110-6440/6441
Pass-Through Card
Reader w/Keypad
3110-7801 Pass-
Through Ruggedized
Card Reader
w/Keypad
Magnetic
stripe card
(high-
coercivity
polyester)
Indoor Only with
Keypad
Indoor/Outdoor
with Keypad
Any of the following:
•
Keypad PIN code only (1-8
digits, then enter # key).
•
Card swipe only.
•
Card and keypad (enter
PIN of 1-8 digits, then
swipe card).
None—ADT-
ordered card comes
pre-programmed
with site code and
user code.
(Possibility of using
credit cards and
driver’s license that
is coded).
ABA card, 34
bits Wiegand:
Reader DIP
switch
settings.
A B C D
on on on off
12-volt strike
(E11 = IN on
ACIU)
Dorado Pass-
Through Card
Reader
∗
3110-7401 Pass-
Through Ruggedized
Card Reader
w/Keypad
Same as above
Indoor/Outdoor
Card swipe
Same as above
Same as above
12-volt strike
(E11 = IN on
ACIU)
Dorado
Insertion Card
Reader
∗
3110-5849/5841
Insert Card Reader
w/Keypad
Same as above
Indoor/Outdoor
with Keypad
Any of the following:
•
Keypad PIN code only (1-8
digits, then enter # key).
•
Card insertion only
(extraction read).
•
Card and keypad (insert
card, enter PIN of 1-8
digits, then remove card).
Same as above, but
cannot accept credit
cards or driver’s
license.
Same as above
12-volt strike
(E11 = IN on
ACIU)
Marlok Keylok
(cylinder w/key
reader and
integral
solenoid)
072-101049/101051
Keylok Mortise
072-101050 Rim
Cylinder Keylok
060-100997 Key In
Knob (D Knob)
Coded Key
Indoor/Outdoor
Coded key is inserted into
Marlok keyreader cylinder. If
key is OK, ACIU provides
voltage for integral solenoid,
permitting key to turn and
release mechanically-linked
latch. (Keylok requires
running wires through door
and installation of a flexible
door cord between door and
its frame.)
None—key comes
pre-coded.
None required
5-volt solenoid
in Keylok
(E11 = OUT on
ACIU)
Marlok
Keyreader
072-038110 Gang-
Mount Keyreader
072-038111 Mullion-
Mount Keyreader
072-038112 Panel-
Mount Keyreader
Coded Key
Indoor Only
Coded key is inserted into
Marlok keyreader cylinder. If
key is OK, ACIU provides
voltage for operating a door
strike.
None—key comes
pre-coded.
None required
12-volt strike
(E11 = IN on
ACIU and
insert 330-ohm
dropping in
series with
TB3-2)
Northern
Computers
Wiegand
Output
Weatherized
Keypad
KP-11-8 BIT
Numerical
Codes
Indoor/Outdoor
Keypad PIN code only (1-8
digits, then enter # key).
N.A.
N.A.
12-volt strike
(E11 = IN on
ACIU)
FOCUS
Operating
Panel
Indoor Only
Enter 6-digit user ID code.
N.A.
N.A.
12-volt strike
(E11 = IN on
ACIU)
∗
Dorado and other mag stripe readers and cards may experience wear, necessitating periodic reader maintenance and eventual card replacement.
Consult vendor literature for details.
∗∗
Refer to vendor literature for environmental and other limitations.
Содержание Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Страница 2: ......
Страница 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Страница 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Страница 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Страница 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Страница 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Страница 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Страница 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Страница 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Страница 210: ...Index Index 6...
Страница 214: ...A 4...
Страница 216: ...9 3l K3471V2 1 00 ADT Security Services Inc One Town Center Road Boca Raton FL 33486 Copyright 1999...