FOCUS 200 PLUS Installation and Setup Guide
21-2
Installation Criteria
Control Unit
Current Draw
Standby
300mA
Alarm
440mA
Temperature Range
32
°
F (0
°
C) to 120
°
F (49
°
C)
Dimensions
18" H x 14-1/2" W x 4.3" D
Maximum Cable Runs
RS-485 Bus #1
4000 Feet
RS-485 Bus #2
4000 Feet
SIM Gateway Trunk
1000 Feet
PID Gateway Trunk (TB2 plus TB3)
1000 Feet
Branch Cable for PID and SIM Sensors
100 Feet
Note:
RS-485 bus and gateway trunk cable lengths may be less, depending on current loading and
voltage drop considerations.
SIM Gateway
Dimensions with Micro PID Housing
3-1/2" H x 3-1/2" W x 1-5/8" D (8.6cm x 8.6cm x 4cm)
Temperature Range
32
°
F (0
°
C) to 120
°
F (49
°
C)
Length of SIM Gateway Trunk
1000 feet (max.)
Gateway Circuit Power Requirement
50ma
Worst Case Voltage @ SIM Gateway
12.lVDC
(End of Standby Period)
(8.4VDC)
Worst Case Voltage @ SIM Sensor
12.0VDC
(End of Standby Period)
(8.3VDC)
SIM Resistor
33k 5% 1/2w
PID Gateway
Dimensions with Standard PID Housing
9-1/4" H x 5" W x 1-5/8" D (23.5cm x l2.7cm x 4.1cm)
Temperature Range
32
°
F (0
°
C) to 120
°
F (49
°
C)
Length of PID Gateway Trunk (TB2 plus TB3)
1000 Feet (max.)
Gateway Circuit Power Requirement
50mA
Minimum Voltage to PID Gateway
12.lVDC
(End of Standby Period)
8.5VDC
Voltage to Farthest PID on Gateway Trunk
12.1VDC (minimum)
(End of Standby Period)
8.5VDC
Worst Case Voltage to Sensor
11.6VDC
(End of Standby Period)
8.0VDC
Sensor Current from PID Standard PID
85mA maximum (current limited)
Maximum PID Loop Resistance
900 ohms
PID Supervisory Current
3mA
PID End-of-Line Resistor
3,010 ohms, 1%, 1/2W
PID Loop Off-Normal Retard
500mSec.
Note:
With AC power off and the battery fully charged the voltage to a sensor being powered by the
system must be greater than the rated minimal voltage of the sensor.
Содержание Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Страница 2: ......
Страница 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Страница 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Страница 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Страница 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Страница 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Страница 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Страница 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Страница 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Страница 210: ...Index Index 6...
Страница 214: ...A 4...
Страница 216: ...9 3l K3471V2 1 00 ADT Security Services Inc One Town Center Road Boca Raton FL 33486 Copyright 1999...