![ADT Commercial Fire & Burglary Alarm System FOCUS 200 PLUS Скачать руководство пользователя страница 146](http://html1.mh-extra.com/html/adt/commercial-fire-and-burglary-alarm-system-focus-200-plus/commercial-fire-and-burglary-alarm-system-focus-200-plus_installation-and-setup-manual_2854006146.webp)
FOCUS 200 PLUS Installation and Setup Guide
13-10
Entry
Number
Description
Function
37 (ACC)
BA Access
Output turns on for 10 seconds when:
•
A valid ID code is entered at the operating panel during the Day
Set condition of the associated BA group.
•
The BA group is turned to Day Set. A typical application is
having the output control a door-strike release mechanism,
permitting access to a controlled area.
38 (HST)
Horn/Strobe
(SIM
Gateway
only).
For use with a horn/strobe that will operate for an FA alarm and,
optionally, also for a BA alarm, as follows:
•
For an FA alarm, strobe flashes continuously and horn operates
for an ongoing series of five 1-second rings followed by a 5-second
pause. Horn/strobe can be silenced only after all FA points
become normal by entering any valid ID code (or 2,2,2,2,2,2);
otherwise, turn-off occurs when 10-minute timeout expires.
•
For a BA alarm, horn sounds continuously unless silenced by
entry a valid ID code (or automatic turn-off occurs for the BA
group that is involved). Strobe does not operate for a BA alarm.
Note: Set option 3 for NFPA temporal pattern (Yes) for this output
point type.
59 (ACD)
Access
Denied
This output point can be used to trigger a camera or activate an
annunciation device in the event that someone uses a card/key
having a code that either:
•
Is not in the system.
•
Does not have Irregular Open, Open or Close access to all BA
groups associated with that ACIU.
•
Does not have the Irregular Open or Open option for any of the
associated BA groups that may be On.
•
Has a Close option and the person attempts to enter outside of
the scheduled open period even though the associated protection
is Off.
When the point is triggered, the output stays on for 10 seconds and
then goes Off.
Output Point Options
The following table describes the output point options:
Option
Associated
Point Type
Function
BA Group
Assignment
All
The number of the BA group that the point will be assigned to.
Bypass
All
Whether bypassing will be permitted by persons with an ID code
having a bypassing privilege.
Fire Point
(Silence)
21
This output point turns on and latches if any fire alarm input
goes into alarm. Ordinarily, the output does not unlatch unless
the alarm-initiating sensor has cleared and the alarm has been
reset. If the Silence option is selected, the output unlatches when
a valid code (or Fire Marshall Code 2,2,2,2,2,2) is entered at any
operating panel.
Содержание Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Страница 2: ......
Страница 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Страница 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Страница 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Страница 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Страница 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Страница 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Страница 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Страница 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Страница 210: ...Index Index 6...
Страница 214: ...A 4...
Страница 216: ...9 3l K3471V2 1 00 ADT Security Services Inc One Town Center Road Boca Raton FL 33486 Copyright 1999...