FOCUS 200 PLUS Installation and Setup Guide
10-18
Level
Privilege
4
Ability to change person/point/BA group descriptions, and privilege level. Ability to change
ID code accessibility to BA group.
5
Ability to bypass fire, holdup, or supervisory points, and to conduct FA sensor test.
6
Service
−
ADT on-premises signal is transmitted to CCC when the ID code is entered and
will lock out all other ID codes. This privilege must be assigned to all Service ID codes, and
is not to be made available to the customer.
7
Operating panel code and/or card/key code is permitted to be changed by person having a
code with Level 4 privilege.
8
Janitor
−
Use of valid card/key will cause the alarm shunting of any Janitor BA points in
the associated BA group(s).
Note: Basic privilege assigned to each code allows user to turn BA protection On and Off for assigned
BA group(s), and to perform tests.
Assigning Access and Privileges for Users
Perform the following steps to enter the card/key access data for a user via the operating panel. See the
ID Codes section for the procedure on entering access capabilities of users using ID Codes.
Enter the Service Code at an operating panel.
< ? Enter choice:
< Lesson
Turn on >
< See alarms
Reset >
< Quit
More >
Action Menu #1 is displayed.
Select More three times to display the last action menu.
< ? Enter choice:
< Sys info
ID codes >
< Name pnt/gps
Load >
< Previous
First >
Action Menu #4 is displayed.
Select ID codes.
< PERSON #1
USER 001
Delete >
< Previous
Change >
< Quit
Next >
Person Data Entry Screen is displayed.
Pressing the [#] key at this screen will bring you to the Enrolling
Key or Card Screen. Also pressing Continue at the last access
screen "ID code may (not) be changed" for BA Group 8 will bring
you to that screen.
< Insert or swipe
key or card
< 1 A 7 7 3 9 6 3
< Quit
Continue >
The Enrolling Key or Card Screen is displayed.
Insert the key or swipe the card in the reader. An 8-digit number
will be displayed.
Select Continue to move to the next screen.
< ? Code and card
will be deleted
< on 08/21
< Quit
Enter >
The Person’s Deletion Date Screen is displayed.
Enter the digits for the month and day after which the person will
be prevented from using the system.
Select Enter to register the date in the system.
< ? Code and card
will be deleted
< on 08/21
< Quit
None >
After you press Enter, that button changes to None.
Select None to delete the date and/or change it.
< ? Code and card
will be deleted
< on 08/21
< Quit
None >
Select Quit to return to the Person Data Entry Screen.
Содержание Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Страница 2: ......
Страница 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Страница 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Страница 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Страница 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Страница 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Страница 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Страница 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Страница 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Страница 210: ...Index Index 6...
Страница 214: ...A 4...
Страница 216: ...9 3l K3471V2 1 00 ADT Security Services Inc One Town Center Road Boca Raton FL 33486 Copyright 1999...