![ADT Commercial Fire & Burglary Alarm System FOCUS 200 PLUS Скачать руководство пользователя страница 193](http://html1.mh-extra.com/html/adt/commercial-fire-and-burglary-alarm-system-focus-200-plus/commercial-fire-and-burglary-alarm-system-focus-200-plus_installation-and-setup-manual_2854006193.webp)
21-1
S E C T I O N 2 1
Specifications
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
In This Section
♦
Electrical/Mechanical Specifications
♦
Installation Criteria
♦
Approvals
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
Electrical/Mechanical Specifications
AC Transformer
For Secondary Wire Runs
Up to 10’ in Length
120V, 60 Hz (Primary)
18V, 60 Hz, 50VA or 72VA (Secondary)
Battery (standby)
Type
12VDC Sealed lead-acid battery
50VA Transformer
7AH min. - 24AH max.
72VA Transformer
7AH min. - 34.4AH max.
Charge Voltage to Battery
Float Charging Voltage
13.65VDC (nominal)
Fuse (FS)
PTC Resetable Fuse (nonreplaceable)
Low-Battery Signal
12.0VDC (nominal)
Low-Battery Cutoff
9.8VDC
Control Unit Power Output to RS-485 Buses
Nominal with AC Connected
13.65VDC
Max. Current
1.0A (Actual allowed is conditioned on
Standby Battery capacity provided; see below)
Fuses Fl (RS-485 #1) and F2 (RS-485 #2)
PTC Resetable Fuse (nonreplaceable)
Maximum RS-485 Bus Load Current
(Standby Condition)
4-Hr. (7AH Battery)
1.0A
24-Hr. (34.4AH Battery)
1.0A
72-Hr. (34.4AH Battery)
132mA
Содержание Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Страница 2: ......
Страница 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Страница 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Страница 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Страница 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Страница 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Страница 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Страница 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Страница 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Страница 210: ...Index Index 6...
Страница 214: ...A 4...
Страница 216: ...9 3l K3471V2 1 00 ADT Security Services Inc One Town Center Road Boca Raton FL 33486 Copyright 1999...